Deutsch|English

Textile-flexible fire / smoke protection curtain TFF

Type: TFF-H

Classification report: 101112218-A (IBS Linz)
tested according to EN 1634-1
Class: E30 - E90
EW20 - EW90
Closing cycles: C - C1 depending on model (e.g. size, weight)
Closing directions: horizontal

 

In general, no wire cable guides are required in the rough opening for our horizontal flexible fabric fire protection closures. Invisible fire protection!

We consider maximum system dimensions up to 7.5 x 15 metres to be standard models. Larger dimensions can be achieved as special systems. As a reference property, we would like to mention the Schwaz City Gallery (Austria) here: 5.6 x 34.3 metres (width x drop length)!

Benefit from our innovative, ball bearing-mounted guide rails, which ensure reliable and low-wear closing and opening even in a draught. Equivalent EI30/EI90 protection objectives are possible with various compensation measures. To enable the pressurised water to divert in the event of sprinkler protection, we have developed a modified fabric for this and offer this as a special model if necessary.

Functionality

When opened, the textile is located on a winding shaft in an enclosure made of galvanised sheet steel above the opening to be closed.

The winding shaft is held in the opened position by a magnetic clamp integrated in the tubular motor. With the help of deflections, the system is closed by concealed wire cable guides in the lateral guide rails by means of gas pressure dampers or by means of a motor (in larger systems). During the closing process, the end strip rides into a recessed profile. The closing speed is approx. 10 - 15 cm per second.

Wiring with functional integrity is not required due to the gravity fail safe principle. Motor controllers, additional accessory components, as well as installation variations can be found in the section Control units.

Installation options

Housing

Wall installation
Housing
Ceiling installation
Housing
via suspensions on the ceiling
Housing

Guide rails

Wall installation
Guide rails
Recess installation
Guide rails
Niche installation
Guide rails

End strips

Galvanised (standard)
End strips

Surfaces

Galvanised sheet steel
(standard configuration)
Surfaces
Powder coating
RAL/DB-Color as per customer wishes (optional)
Surfaces
NCS coating
as per customer wishes (optional)
Surfaces
Stainless steel version
1.4301 (V2A) or 1.4571 (V4A) (optional)
Surfaces